Installation, Operation and Maintenance Manual
MAN720_IMVS2000v2_IOM Rev. 6
MAN720_IMVS2000v2_IOM Rev. 6
Section 8: Table of Alarms
Table of Alarms
Alarm Acronym Composition Squelched By (*) (**) (***)
FST Cycle
Limit
FSCL
The “FST Cycle Count” exceeds the “FST Cycle Limit”
“FST Cyc. Cnt” >= “FST Cyc. Lim.
It is cyclically check (period = 30 seconds).
The check is interrupted during Calibration, Signatures and
PST executions.
Al. FSCL En.” = “No”
“Reset Alarms” command
Power-on Reset
Slow Open
Break Time
SOBT
Last “Maintenance Opening Break Time” is slower than the
“Baseline Opening Break Time” by more than “Opening Time
Hysteresis.
“M. Op. B. T.” > “B. Op. B. T.” * (1 + “Op. Time %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. SOBT En.” = “No”
“M. Op. B. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Fast Open
Break Time
FOBT
Last “Maintenance Opening Break Time” is faster than the “Baseline
Opening Break Time” by more than “Opening Time Hysteresis.
“M. Op. B. T.” < “B. Op. B. T.” * (1 - “Op. Time %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. FOBT En.” = “No”
“M. Op. B. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Slow Open
Travel Time
SOTT
Last “Maintenance Opening Travel Time” is slower than the
“Baseline Opening Travel Time” by more than “Opening Time
Hysteresis.
“M. Op. T. T.” > “B. Op. T. T.” * (1 + “Op. Time %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. SOTT En.” = “No
“M. Op. T. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Fast Open
Travel Time
FOTT
Last “Maintenance Opening Travel Time” is faster than the “Baseline
Opening Travel Time” by more than “Opening Time Hysteresis.
“M. Op. T. T.” < “B. Op. T. T.” * (1 - “Op. Time %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. FOTT En.” = “No”
“M. Op. T. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Slow Close
Break Time
SCBT
Last “Maintenance Closing Break Time” is slower than the “Baseline
Closing Break Time” by more than “Closing Time Hysteresis”.
“M. Cl. B. T.” >= “B. Cl. B. T.” * (1 + “Cl. Time %” /100)
A new Closing FST (without the above condition) resets this alarm.
Al. SCBT En.” = “No”
“M. Cl. B. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Fast Close
Break Time
FCBT
Last “Maintenance Closing Break Time” is faster than the “Baseline
Closing Break Time” by more than “Closing Time Hysteresis”.
“M. Cl. B. T.” < “B. Cl. B. T.” * (1 - “Cl. Time %” /100)
A new Closing FST (without the above condition) resets this alarm.
Al. FCBT En.” = “No”
“M. Cl. B. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Slow Close
Travel Time
SCTT
Last “Maintenance Closing Travel Time” is slower than the “Baseline
Closing Travel Time” by more than “Closing Time Hysteresis.
“M. Cl. T. T.” > “B. Cl. T. T.” * (1 + “Cl. Time %” /100)
A new Closing FST (without the above condition) resets this alarm.
Al. SCTT En.” = “No”
“M. Cl. T. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Fast Close
Travel Time
FCTT
Last “Maintenance Closing Travel Time” is faster than the “Baseline
Closing Travel Time” by more than “Closing Time Hysteresis”.
“M. Cl. T. T.” < “B. Cl. T. T.” * (1 - “Cl. Time %” /100)
A new Closing FST (without the above condition) resets this alarm.
Al. FCTT En.” = “No”
“M. Cl. T. T.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Open High
Break Pressure
OHBP
Last “Maintenance Opening Break Pressure” is greater than the
“Baseline Opening Break Pressure” by more than “FST Pressure
Hysteresis”.
“M. Op. B. P.” > “B. Op. B. P.” * (1 + “FST Pr. %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. OHB En.” = “No
“M. Op. B. P.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
Open Low
Break Pressure
OLBP
Last “Maintenance Opening Break Pressure” is lower than the
“Baseline Opening Break Pressure” by more than “PST Pressure
Hysteresis”.
“M. Op. B. P.” < “B. Op. B. P.” * (1 - “FST Pr. %” /100)
A new Opening FST (without the above condition) resets this alarm.
Al. OLBP En.” = “No”
“M. Op. B. P.” = 0
“Reset Alarms” command
Power-on Reset
Calibration
Baseline Signature
72