Fan Motor Options
Model Tap #
Default Factory
Motor Setting
CFM
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
CF036
1 FO 984 954 927 889 814 774 742 725 706 669
2 DH 1135 1105 1080 1054 1017 949 910 876 846 832
3 PL 1032 1001 974 947 882 831 797 766 750 732
4 FL 1295 1270 1244 1219 1200 1175 1147 1067 1021 953
5 EH 1386 1362 1335 1311 1289 1266 1243 1220 1047 951
CF042
1 FO 1088 1060 1032 996 959 928 895 865 778 739
2 DH 1284 1259 1234 1210 1185 1149 1124 1099 1069 1032
3 PL 1218 1191 1166 1142 1104 1078 1049 1011 982 950
4 FL 1490 1466 1442 1419 1397 1375 1342 1314 1289 1227
5 EH 1568 1543 1520 1497 1475 1452 1427 1394 1348 1268
CF048
1 FO 1213 1183 1156 1129 1104 1079 1048 1016 897 858
2 DH 1458 1431 1408 1386 1363 1341 1317 1293 1267 1240
3 PL 1318 1293 1265 1239 1215 1190 1165 1135 1104 983
4 FL 1702 1678 1657 1633 1606 1587 1566 1541 1513 1454
5 EH 1801 1775 1753 1728 1704 1683 1658 1628 1571 1493
CF060
1 FO 1561 1519 1488 1459 1415 1385 1338 1301 1263 1217 1177 1119
2 DH 1848 1821 1795 1757 1730 1700 1667 1639 1609 1567 1531 1497
3 PL 1677 1648 1608 1579 1550 1510 1482 1450 1402 1368 1323 1285
4 FL 2142 2116 2089 2057 2029 2009 1978 1942 1913 1883 1852 1812
5 EH 2231 2202 2176 2147 2119 2090 2063 2036 2003 1971 1941 1907
CF070
1 FO 1647 1598 1562 1531 1488 1456 1424 1379 1347 1311 1259 1158
2 DH 1951 1923 1884 1856 1828 1794 1758 1731 1700 1662 1632 1599
3 PL 1832 1795 1762 1733 1704 1662 1636 1605 1562 1530 1499 1456
4 FL 2255 2221 2194 2164 2137 2109 2073 2046 2018 1991 1957 1920
5 EH 2497 2467 2440 2410 2379 2350 2319 2290 2262 2233 2202 2151
Note: DH = Dehumidification, EH = Electric Heat (when installed), FL = Full Load, FO = Fan Only, and PL = Part Load
Table 12 Constant Torque Motor Performance Data—Vertical Configuration
Off delay = 30 seconds = After receiving an OFF command
motor will continue running for 30 seconds. CFM based on
wet coil and 1" Merv 5 Throwaway. DH is the default tap for
Dehumidification.
44 |
CF Series Heat Pumps — 8733846299 (2024/11)