D9068 | Operation and Installation Guide | 5.0 Programming
46
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
Figure 27: 4/2 Point Report Example
12
1
2
1 - Digit 1 (D1) is the event type
identifier. The event type in this
example is 1: FIRE ALRM.
2 - Digit 2 (D2) is the point
identifier. The point identifier
identifies the point assigned to the
D1 event type. The event type in
this example is assigned to Point 2.
The point range is 1 to 5.
To set the event and point format of a
report:
1. At the Prog Formats submenu, press
[1] to select
1: 4/2 POINT RPT. The window shows:
4/2 POINT RPT
1: EVENTS
2: ZONES 1 TO 9
3: ZONE 10 D2
2. Press [1] to select 1: EVENTS. The
window shows:
4/2 POINT RPT
1: FIRE ALRM D1
2: FIRE RSTR D1
3: WATERFLOW D1
4: SUPERVISE D1
5: TROUBLE D1
6: TRBL RSTR D1
7: DISABLE D1
8: DSBL RSTR D1
9: MONITOR D1
3. D1 refers to Digit number 1. Press
the number key that corresponds with
your selection of event type. In this
example, 1: FIRE ALRM D1 is selected.
The window shows:
FIRE ALRM D1 (_____)
0-9, <TEST>:
4. The current setting appears in
parentheses on the first line. Press
[# Command] to verify your selection.
5. If you prefer to assign a hexadecimal
value, press [Test]. The window
shows:
SELECT HEX CODE
1: HEX A
2: HEX B
3: HEX C
4: HEX D
5: HEX E
6: HEX F
In 4/2 formats, HEX A reports
as 0 (zero).
6. Press the number key that corresponds
with your selection.
7. Press [# Command] to verify the
selection, then press [* Clear] to
return to the 4/2 Point Rpt submenu.