D9068 | Operation and Installation Guide | Appendix C: Fire Communicator Report
Summary
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
Table 14: Reporting Summaries
Point-Related Events
Report
Description
SIA
Code
SIA
Description
Contact
ID Code
Contact ID
Description
4/2
Code
Default
Values
Modem IIIa
2
Description
Point Fire
Alarm
FA pppp
Fire Alarm
1 110 aa
ppp
Fire Alarm
0P
Fire Alarm Point =
ppp
Point Water-
flow Alarm
SA pppp
Sprinkler
Alarm
1 113 aa
ppp
Waterflow
0P
Fire Alarm Point =
ppp
Point
Supervisory
Alarm
SS pppp
Sprinkler
Supervisory
1 200 aa
ppp
Fire
Supervisory
0P
Fire Supervision
Point = ppp
Point Monitor
Alarm
UA pppp
Untyped Zone
Alarm
1 140 aa
ppp
General
Alarm
0P
Alarm Point = ppp
Point Fire
Trouble
FT pppp
Fire Trouble
1 373 aa
ppp
Fire
Trouble
6P
Fire Trouble Point =
ppp
Point Water-
flow Trouble
ST pppp
Sprinkler
Trouble
1 373 aa
ppp
Fire
Trouble
6P
Fire Trouble Point =
ppp
Point
Supervisory
Trouble
ST pppp
Sprinkler
Trouble
1 373 aa
ppp
Fire
Trouble
6P
Fire Trouble Point =
ppp
Point Monitor
Trouble
UT pppp
Untyped Zone
Trouble
1 373 aa
ppp
Fire
Trouble
6P
Trouble Point = ppp
Point Fire
Alarm Restore
FR pppp
Fire
Restoral
3 110 aa
ppp
Fire Alarm
3P
Fire Restoral Point
= ppp
Point Water-
flow Restore
SH pppp
Sprinkler
Alarm
Restore
3 113 aa
ppp
Waterflow
3P
Fire Restoral Point
= ppp
Point
Supervisory
Restore
SR pppp
Sprinkler
Restoral
3 200 aa
ppp
Fire
Supervisory
3P
Fire Restoral Point
= ppp
Point Monitor
Restore
UR pppp
Untyped Zone
Restoral
3 140 aa
ppp
General
Alarm
3P
Restoral From Alarm
Point = ppp
Point Fire
Trouble
Restore
FJ pppp
Fire Trouble
Restore
3 373 aa
ppp
Fire
Trouble
3P
Fire Trouble
Restoral Point = ppp
Point Water-
flow Trouble
Restore
SJ pppp
Sprinkler
Trouble
Restore
3 373 aa
ppp
Fire
Trouble
3P
Fire Trouble
Restoral Point = ppp
Point
Supervisory
Trouble
Restore
SJ pppp
Sprinkler
Trouble
Restore
3 373 aa
ppp
Fire
Trouble
3P
Fire Trouble
Restoral Point = ppp
Point Monitor
Trouble
Restore
UJ pppp
Untyped
Trouble
Restore
3 373 aa
ppp
Fire
Trouble
3P
Restoral Point = ppp
Open Reset
OR iii
Disarm From
Alarm
1 401 aa
iii
O/C By User
9F
Sensor Reset ID =
iii
Low Battery
YT
System
Battery
Trouble
1 302 aa
000
Low System
Battery
F9
Battery Low
Low Battery
Restore
YR
System
Battery
Restoral
3 302 aa
000
Low System
Battery
E9
Battery Restoral
Refer to Note 1 through Note 9 above.