EasyManua.ls Logo

Bosch PRA-CSE - Page 127

Bosch PRA-CSE
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PRAESENSA Multifunction power supply, large | PRA-MPS3 | en 127
Bosch Security Systems B.V. Installation manual 2019.11 | V1.00 |
Power transfer
Active mode, all outputs loaded
Per active port
Per active SFP port
<1000W
0.4W
0.7W
Lifeline / power save interface
Audio level (100V / 70V mode)
Frequency response (+0 / -3 dB)
Signal to Noise Ratio (SNR)
0dBV / -6dBV
200Hz to 15kHz
90dBA
EN54‑4 related information
Maximum battery capacity 230 Ah
Lowest discharge voltage 9 V
Continuous output current
(I max. a / I max. b / I min.)
48 VDC outputs (1-3)
24 VDC output
PoE output (1-2)
Lifeline DC outputs (1-3)
5.5 A / 5.5 A / 0 A
0.7 A / 0.7 A / 0 A
0.3 A / 0.3 A / 0 A
0.7 A / 0.7 A / 0 A
Output voltage range
48 VDC outputs (1-3)
24 VDC output
PoE output (1-2)
Lifeline DC outputs (1-3)
46 to 50 V
23 to 25 V
44 to 57 V
9 to 18 V
Maximum impedance of battery circuit
230 Ah battery
180 Ah battery
140 Ah battery
100 Ah battery
7.1 mohm
8.6 mohm
9.8 mohm
11.0 mohm
Control interface
Control input contacts (1-8)
Principle
Galvanic isolation
Supervision
Contact closed
Contact open
Cable fault detection
Minimum hold time
Maximum voltage to ground
Contact closure
No
Resistance
measurement
8 to 12kohm
18 to 22kohm
<2.5kohm/>50kohm
100ms
24V
Control output contacts (1-8)
Principle
Galvanic isolation
Contact switch over
(Relay SPDT)
Yes