5.4.3 Power consumption
The following table gives an overview of the power demand of the PRAESENSA devices for the
different operating conditions.
Device Device elements Power
consumption
[W]
Power from
battery [W]
Current
from
battery [A]
PRA-SCL System controller
+ per active RJ45 port
3.9
0.4
4.2
0.5
0.35
0.04
PRA-CSLD /
PRA-CSLW
Call station
+ per active RJ45 port
+ per extension PRA-CSE
+ with alarm option
4.2
0.5
0.1
1.2
5.0
0.6
0.1
1.5
0.42
0.05
0.01
0.12
PRA-AD604 Amplifier (sleep)
Amplifier (snooze)
Amplifier (active, idle)
Amplifier (active, low power)
Amplifier (active, full power)
+ per active RJ45 port
6.0
8.0
32
52
220
0.4
6.0
8.5
39
64
250
0.4
0.50
0.71
3.25
5.33
20.83
0.03
PRA-AD608 Amplifier (sleep)
Amplifier (snooze)
Amplifier (active, idle)
Amplifier (active, low power)
Amplifier (active, full power)
+ per active RJ45 port
6.0
8.4
38
70
242
0.4
6.0
9.2
48
88
274
0.4
0.50
0.77
4.00
7.33
22.83
0.03
PRA-ES8P2S Ethernet switch
+ per active RJ45 port
+ per active SFP port
+ PoE load
7.0
0.4
0.7
load
8.4
0.5
0.8
1.2 x load
0.70
0.04
0.07
0.1 x load
PRA-MPS3 Multifunction power supply
+ per active RJ45 port
+ per active SFP port
5.2
0.4
0.7
5.2
0.4
0.7
0.43
0.03
0.06

Table of Contents