126 en | Multifunction power supply, large | PRA-MPS3 PRAESENSA
2019.11 | V1.00 | Installation manual Bosch Security Systems B.V.
11.7 Technical data
Electrical
Power transfer
Mains power supply input
Input voltage range
Input voltage tolerance
Frequency range
Inrush current
Power factor (PF)
Leakage current to safety ground
115 to 240VRMS
102 to 264VRMS
50 to 60Hz
<20A
0.9 to 1.0
<0.75 mA (120V),
<1.5 mA (240V)
Battery power supply input
Nominal DC input voltage
DC input voltage tolerance
Maximum current
Under-voltage protection
12.6V
9 to 15V
90A
<9V
Battery charger
Nominal charging current
Nominal float voltage
Float voltage control
Temperature sensor NTC
Charging temperature range
8.5A
13.5V
-21.9mV/°C
10kohm / β = 3984K
-15 to 50°C
48VDC outputs (1‑3)
Nominal DC output voltage
Maximum continuous current
Maximum peak current
48V
5.5A
7.0A
24VDC output
Nominal DC output voltage
Maximum continuous current
Maximum peak current
24V
0.7A
0.9A
Lifeline DC outputs (1‑3)
Nominal DC output voltage
Maximum continuous current
Maximum peak current
18V
0.7A
1.0A
Power over Ethernet (PoE 1‑2)
Nominal DC output voltage
Standard
Maximum PD load
48V
IEE802.3af (mode B)
12.95W
Power consumption
Mains powered
Active mode, all outputs loaded
Battery powered
Unloaded
<1000W
5.2W