134 en | Programming options PRAESENSA
2021.12.21 | V0.15b | F.01U.402.882
Underwriters Laboratories Listing Document (ULLD)
Bosch Security Systems B.V.
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Yes Amplifier channel
supervision
Enable/disable Set to enable
Yes Loudspeaker line
supervision
Enable/disable Set to enable
Yes Overload supervision Enable/disable Set to enable
* Single = ClassB; Dual is dual ClassB; Loop = ClassA
Multifunction power supply
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Device options Multifunction power supply
General Yes AC power supervision Enable/disable Set to enable
Yes Battery supervision Enable/disable Set to enable
Yes Emergency relevant Enable/disable Set to enable
Control inputs
Function Yes Local BGM source Selection Ancillary
function
Yes Local BGM on/off Selection Ancillary
function
Yes Local BGM volume
control
Selection Ancillary
function
Call station
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Device options Call station
Settings >
General
Yes Class Normal
Emergency
Mass notification
Select “Mass
notification”
for ACU/LOC
Yes Expected PoE inputs Selection (0‑2) Select 2 for
ACU/LOC
Yes Emergency relevant Enable/disable Set to enable