PRAESENSA Programming options | en 135
Bosch Security Systems B.V.
Underwriters Laboratories Listing Document (ULLD)
2021.12.21 | V0.15b | F.01U.402.882
Topic
Configure /
programming
Feature or option Permitted
in UL2572
(Y/N/
required)
Possible settings Value Settings
permitted in
UL2572
Settings >
Functions
(Normal)
Yes Alert messages Enable/disable Not allowed
on PRA-CSLD
or PRA-CSLW
Yes Trouble log Enable/disable Not allowed
on PRA-CSLD
or PRA-CSLW
Settings > Audio
inputs
Yes Microphone Enable/disable Set to enable
for ACU/LOC
Yes Supervision Enable/disable Set to enable
for ACU/LOC
Yes Input gain Selection (-10 to 10
dB)
Make sure
speech
intelligibility
is sufficient
Settings > Extension
Function Yes Make announcement Selection Allowed *)
Yes Make announcement with
zone selection
Selection Allowed *)
Yes Transfer of control Selection Select for
ACU/LOC
*) Not allowed in combination with live speech announcements when
multiple PRA-FRP are employed in the system.
Emergency group Yes Group Selection Select for
ACU/LOC
Yes Overrule control request Selection Select for
ACU/LOC
Yes Group name Enter / rename name Enter for
ACU/LOC
Yes Default in control Selection Select for
ACU/LOC
Yes Grant control timeout Selection (1‑90
seconds)
Select for
ACU/LOC
(default 30
sec.)