System settings (Service menu – Settings)
Logamatic EMS – 6 720 801 387 (2011/05)
30
6
6.3 Boiler data
B Turn the rotary selector to the left until boiler data is selected.
B Press to select boiler data.
The menu SETTINGS\BOILER is opened.
Menu item Input range
Standard
setting
Other information
Boiler pump after-run time
after burner stops?
deactivated,
1 to 60
minutes,
24 hours
5 min Setting is only possible with boilers
with internal pump.
1)
1) Not possible or not available with pumps with UBA1.x.
Set the pump logic
temperature.
0 to 65 °C 47 °C Setting only possible in conjunction
with BRM10.
Table 13 Navigator for service menu SETTINGS\BOILER
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1