EasyManua.ls Logo

Bosch RC35 - Page 58

Bosch RC35
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Logamatic EMS – 6 720 801 387 (2011/05)
58
10
A2x 829 RC20/RF as
remote
control.
RC20/RF unable to
transmit data to RC35.
Therefore no room
temperature
compensated control
possible for this heating
circuit.
RC20/RF address
incorrectly allocated
in RC35 or not
installed in RC35.
B Set
programming
unit parameters in
the RC35 to
RC20/RF.
B Check the
assignment of the
RC20/RF.
A2x 830 Low battery
for wireless
oper. unit
HCx.
No effect if the battery is
replaced in time.
Battery in RC20/RF
for HCx is low.
B Replace batteries.
A2x 839 No radio
communicati
on with
programmin
g unit HKx.
Radio fault.
Since the actual room
temperature is missing,
the following cannot
function:
Room influence
Switching point
optimisation
The RFM20 operates
with the last values set
on the remote control
unit.
RC20/RF is outside
the range of
reception.
B Bring the RC20/
RF within the
range of reception.
Heating system has
been switched off.
B Switch on the
heating system.
When RFM20 was
replaced, the RC20/
RF was not
registered on the
new RFM20.
B Register the
RC20/RF (see
documentation for
RC20/RF).
A2x 842 Frost
protection
selected but
no frost
mode HKx.
Since the actual room
temperature is missing,
the following cannot
function:
Room influence
Switching point
optimisation
The EMS operates with
the last values set on the
remote control unit.
No programming unit
/ remote control unit
assigned, although
frost protection is
set to room
temperature.
B Check
programming
unit parameters.
B Possibly change
over Frost
protection to
outside
temperature.
A2x 843 Room
control
selected but
no
rem.contr.
HCx.
No programming
unit/remote
programmer
allocated, although
room temperature
compensated is
set.
B Check
programming
unit parameters.
B If required switch
to outside
temperature
compensated.
SC FC Error display
Effect on control
characteristics Possible cause Remedy
Table 23 Fault table

Table of Contents

Related product manuals