ctrlX SAFETY | Commissioning 35/83
DOK-XSAFE*-SAFEX-C.1XC-IT03-EN-P, Edition 03, Bosch Rexroth AG
7.4.3 Reset function
Tabelle 18: Reset functions
Functional unit General reset Internal reset Function
Fatal error X Reset error
Alarm X X Reset alarm
Monitoring functions X X Reset of an addressed
monitoring function
Flip-flop X X Status = Reset
Timer X X Timer = 0
Note: The overview provided above depicts the possibilities of the reset functions. More
detailed information on block and logic functions is available in the “Programming manual for
ctrlX SAFETY SAFEX-C.1* devices with ctrlX SAFETY Engineering DOK-XSAFE*-SAFEX-
C.1XC-PRxx-DE-P.
The status of the monitoring functions is re-initialized after a reset.
• If the parameterized limits are exceeded, process values do not lead to any change in the
output status of the monitoring function.
• Time-based functions - Timers reset the output status of the monitoring function. A
response only takes place when the parameterized limit values are exceeded again.
Fig. 7: Reset function 1: Process value (position) > no change of the output status for a reset in
the alarm state
Fig. 8: Reset function 2: Process value (speed) > no change of the output status for a reset in the
alarm state.