EasyManua.ls Logo

Bosch Rexroth EFC 3600 - Main Circuit Wiring Diagram

Bosch Rexroth EFC 3600
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4 Fe UL Ratings and Dimensions_45K0 to 160K
Description
Sym‐
bol
Unit 45K0 55K0 75K0 90K0 110K 132K 160K
Mass m kg 33.2 33.8 50.9 52.5 96.5 100 102
Device height
(UL)
6)
H mm 602 682 850
Device depth
(UL)
7)
T mm 260 290 360
Device width
(UL)
8)
B mm 364 455 570
Rated input cur‐
rent (UL)
I
LN
A 101 117 157 187 226 280 338
Branch circuit
protection fuse
(UL)
9)
I
LN
A 150 175 225 300.0 300 2x250 2x300
Required wire
size according
to
EN 60204-1
10)
A
LN
mm
2
12)
50
13)
50
14)
35
50
70/2*3
5
50
95/2*5
0
120/2*
50
70/2*3
5
120/2*5
0
150/2*7
0
95/2*50
150/2*
70
240/2*
95
150/2*
70
240/2*
95
2*120
150/2*
70
2*120
-
240
Required wire
size according
to UL 508 A (in‐
ternal wiring);
(UL)
11)
A
LN
AW
G
1 1/0
3/0/
2*AW
G1
250mc
mil/
2*AWG
1/0
2*AW
G3/
0
2*AW
G3/
0
2*AW
G4/
0
Output current
(UL)
I
out
A 95 110 152 183 223 265 325
Fig.3-4: Fe - UL Ratings and Dimensions_45K0 to 160K
Bosch Rexroth AG
Ratings and Dimensions
DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
32/65

Table of Contents

Other manuals for Bosch Rexroth EFC 3600

Related product manuals