3.6 Fv UL Ratings and Dimensions_0K40 to 7K50
Description
Sym‐
bol
Unit 0K40 0K75 1K50 2K20 4K00 5K50 7K50
Mass m kg 2.7 2.7 2.7 2.8 4.8 4.9 4.9
Device height (UL)
6)
H mm 315 380
Device depth (UL)
7)
T mm 127 162
Device width (UL)
8)
B mm 125 150
Rated input current
(UL)
I
LN
A 3.0 3.7 5.1 7.6 16 16.5 23.5
Branch circuit protec‐
tion fuse (UL)
9)
I
LN
A 6 6 10 16 25 40 40
Required wire size
according to
EN 60204-1
10)
A
LN
mm
2
12)
1.5
13)
0.75
14)
0.75
1.5
1
1
1.5
1
1
1.5
1
1
1.5
1.5
1.5
2.5
2.5
2.5
4
4
2.5
Required wire size
according to UL 508
A (internal wiring);
(UL)
11)
A
LN
AWG 14 14 14 14 12 10 10
Output current (UL)
I
out
A 1.3 2.5 4 5.5 10 13 17
Fig.3-6: Fv - UL Ratings and Dimensions_04K0 to 7K50
Bosch Rexroth AG
Ratings and Dimensions
DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
34/65

Table of Contents

Other manuals for Bosch Rexroth EFC 3600