3.5 Fv UL Ratings and Dimensions in Common
Description Symbol Unit Data
Listing according to UL standard (UL) – – UL 508 C
UL files (UL) – – NMMS.E328841
Enclosure – – Open type
Pollution degree (UL) – – 2
Ambient temperature with nominal data (UL)
T
amax
°C 40
Ambient temperature with reduced nominal
data (UL)
T
amax_red
°C 50
Minimum distance on the top of the device
1)
d
top
mm 150
Minimum distance on the bottom of the de‐
vice
2)
d
bot
mm 150
Horizontal spacing on the device
3)
d
hor
mm 0
Short circuit current rating (UL) SCCR A rms
5000 (0K75 to 37K0)
42000 (45K0 to 90K0)
Rated input voltage, power (UL)
4)
U
LN_nenn
V 3 x AC 380...480
Tolerance rated input voltage (UL) % -15...+10
Input frequency (UL)
f
LN
Hz 50...60
Tolerance input frequency (UL) Hz ± 5
Field wiring material (material; conductor
temperature; class)
– –
Copper; 60/75 °C
(0K75 to 18K5)
Copper; 75 °C (22K0
to 90K0)
Output voltage (UL)
U
out
V
Corresponding to in‐
put voltage
Output frequency range (UL)
5)
f
out
Hz 0...400
Fig.3-5: Fv - UL Ratings and Dimensions in Common
DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
Bosch Rexroth AG
Ratings and Dimensions
33/65