Loading...
5.2.2 Allowed Mounting Position
a Mounting surface g Direction of gravitational force
G1 Normal mounting positions. The natural
convection supports the forced cooling
air current. This avoids the generation of
pockets of heat in the component.
G2 180° to normal mounting position
G3 Turned by 90° from vertical to horizontal
mounting position
G4 Bottom mounting; mounting sur‐
face on bottom of control cabinet
G5 Top mounting; mounting surface at top of
control cabinet
Fig.5-1: Allowed mounting position
5.2.3 Sizing of Enclosure and Control Cabinet
Multiple-Line Design of the Control Cabinet
Arrangement of the devices, air guides/drip protections, fans
Pay particular attention to the maximum allowed air intake temperature of devices
when they are arranged in multiple lines in the control cabinet.
If possible, place devices with a high degree of power dissipation (e.g. supply units with
braking resistors, DC bus resistor units)
in the top line and
near the outlet air aperture to the cooling unit
Mount air guides between the lines to
protect the devices in the upper lines against the warm outlet air of the devices be‐
neath and
protect the devices beneath against penetration of liquids (e.g. dripping condensa‐
tion water or leaking cooling liquid)
DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
Bosch Rexroth AG
Instructions for Use
41/65