Rexroth connection diagrams are only to be used for producing installation
circuit diagrams! The machine manufacturer’s installation circuit diagrams
must be used for wiring the installation!
Lay signal lines separately from the load resistance lines because of the occurrence
of interference.
Transmit analog signals (e.g. command values, actual values) via shielded lines.
Do not connect mains, DC bus or power cores to low voltages or allow them to come
into contact with these.
When carrying out a high voltage test or an applied-overvoltage withstand test on
the machine’s electrical equipment, disconnect all connections to the devices. This
protects the electronic components (allowed in accordance with EN 60204-1). Dur‐
ing their routine testing, Rexroth frequency converters are tested for high voltage (in
accordance with EN 61800-5-1:2007, section 5.2.3.2) and insulation (in accordance
with EN 60204-1:2006, section 18.3).
Risk of damage to the frequency converter by con‐
necting and disconnecting live connections!
NOTICE
Do not connect and disconnect live connections.
Bosch Rexroth AG
Instructions for Use
DOK-RCON01-REX*F*UL***-IN01-EN-P
Rexroth Frequency Converters
40/65