8.10 Group E4: Error and Protection
E4.01 Overvoltage prevention setting
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
0: Both disabled
1: Stall protection enabled, braking disabled
2: Stall protection disabled, braking enabled
When [E4.01]=0 / 1, the brake chopper will not work even its action point is reached.
When [E4.01]=2, the brake chopper is enabled with the set braking ratio if its action
point is reached, no matter the frequency converter is in stop or running mode.
Two factors decide the switching pattern: Maximum duty cycle (duty ratio) and hystere‐
sis voltage.
Maximum duty cycle
The switching time of the brake chopper is limited with parameter [S3.21]. If the value is
set too low, over voltage errors may happen during braking.
The time t2=1 / 100 Hz=10ms
The time t1=t2 x [S3.21] / 100 %
If the switching of the brake chopper is controlled by the maximum duty cycle, the
switching pattern is shown as below:
Fig.8-41: Switching pattern_Maximum duty cycle
Hysteresis Voltage
The hysteresis voltage of braking is fixed as below: