5.11 Notes on Control Circuit Wiring
Terminal GND is the common terminal for analog signals, and SC is the common
terminal for digital signals. Do not ground these terminals. Shielded or twisted-pair
cables should be used for control circuit terminals wiring and must be separated
from the wiring of main circuit and high current circuits (including the control circuit of
200 V relay).
Please strip the wire insulation for wiring of the control circuit, according to the di‐
mensions given below. Too long stripping may cause short circuit of adjacent wires;
too short stripping may lead to wires becoming loose.
Fig.5-11: Wire stripping length
Disconnection of cables or damage of screws may cause incorrect operation if
screws are not fixed correctly.
5.12 Control Circuit Terminals
Fig.5-12: Control circuit terminals
The sequence of the label and the terminals is as indicated by arrows in
the above figure.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Mounting and Installation
37/235