EasyManua.ls Logo

Bosch Rexroth EFC 3600 - Main Circuit Wiring Steps

Bosch Rexroth EFC 3600
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.9.3 Recommendation for Design of the Fuses
International except for USA/Canada:
Class gL-gG; 500 V, 690 V; design NH, D (DIAZED) or D0 (NEOZED).
In the case of error (e.g. ground fault at connections L+, L-), fuses of
characteristic gL (general-purpose fuse link for cables and lines) and
gG (general-purpose fuse link for general installations) protect the lines
in the frequency converter system.
To protect the semiconductors in the input of supply units and frequen‐
cy converters, you can use fuses of characteristic gR.
USA/Canada: Class J; 600 V
5.10 Main Circuit Wiring Steps
Fig.5-10: Main circuit wiring steps
Bosch Rexroth AG
Mounting and Installation
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
36/235

Table of Contents

Other manuals for Bosch Rexroth EFC 3600