7.3 EFC 3600 Basic Parameter Fast Settings
Using the operating panel to set the necessary parameters based on the application
loads and specifications allows the frequency converter to start rapidly. A basic generic
parameter fast setting table is given below.
Set [b0.02]=4 with Func and Set keys to show "-St-" group.
For parameter attributes, see chapter 17.2.1 "Description of Attribute
Symbols in Parameter Tables" on page 195.
Function
code
Name
Setting
range
Min.
unit
Factory
default
Attributes
[b0.21] Carrier frequency 1 ~ 15 kHz 1 kHz 4 kHz Run/Stop
[b1.00] First frequency set‐
ting source
0 ~ 6 1 0 Stop
[b1.02] First Run command
source
0 ~ 2 1 0 Stop
[b1.05] Max. frequency 50.00 ~ 400.00
Hz
0.01 Hz 50.00 Hz Stop
[b1.06] Upper frequency [b1.07] ~ [b1.05] 0.01 Hz 50.00 Hz Run/Stop
[b1.07] Lowest frequency 0.00 ~ [b1.06] 0.01 Hz 0.00 Hz Run/Stop
[b1.04] Digital set frequency [b1.07] ~ [b1.06] 0.01 Hz 50.00 Hz Run/Stop
[b1.10] Direction control 0 ~ 3 1 0 Stop
[b1.20] Acceleration time 1 0.1 ~ 6000.0s 0.1s 5.0s Run/Stop
[b1.21] Deceleration time 1 0.1 ~ 6000.0s 0.1s 5.0s Run/Stop
[b1.22] Acceleration/deceler‐
ation curve mode
0 ~ 1 1 0 Stop
[b1.30] Starting mode 0 ~ 2 1 0 Stop
[b1.40] Stopping mode 0 ~ 2 1 0 Stop
[S0.00] V/F curve mode 0 ~ 2 1 0 Stop
[S2.00] Rated motor frequen‐
cy
5.00 ~ 400.00
Hz
0.01 Hz 50.00 Hz Stop
[S2.01] Rated motor rotation
speed
1 ~ 30000 rpm 1 rpm Depending
on model
Stop
[S2.02] Rated motor power 0.1 ~ 1000.0 kW 0.1 kW Depending
on model
Stop
Bosch Rexroth AG
Commissioning
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
50/235