S3.35 Stop by Stop key
Setting range
0: Only valid for operating panel control
1: Valid for all control means
Minimum unit 1
Factory default 1
8.6 Group E0: Input Terminal Parameters
E0.00 2-wire / 3-wire running control
Setting range 0 ~ 2
Minimum unit 1
Factory default 0
In order to run the frequency converter with "2-wire / 3-wire running control", [b1.02] /
[b1.17] needs to be set as 1.
For example: one terminal is assigned as FWD ( [E0.01]=23) and connected to K1; an‐
other terminal is assigned as REV ( [E0.02]=24) and connected to K2.
[E0.00]=0: Forward / Stop, Reverse / Stop
Fig.8-27: 2-wire control_1
K1 K2 Running status
Inactive Inactive Stop
Inactive Active Reverse
Active Inactive Forward
Active Active Stop
If both terminals are active at the same time, the frequency converter
stops according to the stopping mode configured [b1.40] and both direc‐
tions LEDs (FWD and REV) are switched on.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings
91/235