7.2 Commissioning Process
Step Operation Description
1
Rotate the potentiometer counterclock‐
wise (leftwards) to the greatest extent
The initial frequency value is 0.00
2 Press Run key
Enter the command for running, with
0.00 displayed
3
Rotate the potentiometer clockwise
(rightwards) slowly and the displayed
value starts to change, until 5.00 is dis‐
played
The motor starts to run
4
Observe:
Whether the motor runs in the correct
direction
Whether the motor runs smoothly
Whether there is any abnormal noise
or problem
Observe the running, and immediately
stop the motor by shutting off the pow‐
er if any abnormality occurs. Restart
commissioning only after the fault
causes have been removed
5
Rotate the potentiometer clockwise
(rightwards)
The motor accelerates
6
Rotate the potentiometer counterclock‐
wise (leftwards)
The motor decelerates
7 Press Stop key
When commissioning is complete, the
command for stopping is activated.
The frequency converter is ready for
normal operation.
Fig.7-1: Commissioning process