● [E0.00]=1: Forward / Reverse, RUN / STOP
Fig.8-28: 2-wire control_2
K1 K2 Running status
Inactive Inactive Stop
Inactive Active Stop
Active Inactive Forward
Active Active Reverse
● [E0.00]=2: 3-wire control
An additional terminal needs to be configured as "3-wire running control" and con‐
nected as below:
Fig.8-29: 3-wire control
– K1 is RUN command source
– K2 is used for direction selection
– 0=forward
– 1=reverse
– K3 is STOP command source (3-wire mode N.C. terminal)
– FWD input is edge-sensitive
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
92/235