Minimum immunity requirements for PDSs intended for use in the second environment
Port Phenomenon
Basic
standard
for test
method
Level
Performance
(acceptance)
criterion
Enclosure port
ESD
IEC
61000-4-2
4 kV CD or 8 kV AD
if CD impossible
B
Radio-frequency electro‐
magnetic field, amplitude
modulated
IEC
61000-4-3
80 to 1000 MHz 10
V/m
1.4 to 2.0 GHz 3 V/m
2.0 to 2.7 GHz 1 V/m
80 % AM (1 kHz)
A
Power ports
Fast transient-burst
IEC
61000-4-4
2 kV/5 kHz B
Surge 1.2/50 μs, 8/20 μs
IEC
61000-4-5
1 kV
a
, 2 kV
b
B
Conducted radio-frequen‐
cy common mode
IEC
61000-4-6
0.15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Power
interfaces
Fast transient-burst
IEC
61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Signal
interfaces
Fast transient-burst
IEC
61000-4-4
1 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequen‐
cy common mode
IEC
61000-4-6
0.15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Ports of process
measurement
control lines
Fast transient-burst
IEC
61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequen‐
cy common mode
IEC
61000-4-6
0.15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Fig.11-1: Minimum immunity requirements for PDSs intended for use in the second
environment
Bosch Rexroth AG
Electromagnetic Compatibility (EMC)
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
148/235