IEC / EN
61800-3
CISPR 11 Explanation
In this
document
Curves of
limit value
characteristic
Category C4
2
nd
environment
None
One of the following 3
requirements must have been
fulfilled:
● Mains connection
current>400 A, IT mains or
required dynamic drive
behavior not reached by
means of EMC filter.
● Adjust limit values to use and
operation on site.
● User has to carry out and
provide evidence of EMC
planning.
None –
Category C3
2
nd
environment
Class A;
group 2,
I>100 A
Limit value in industrial areas to
be complied with for
applications operated at supply
mains with nominal
currents>100 A
A2.1
1.1
1.2
Category C3
2
nd
environment
Class A;
group 2,
I≤100 A
Limit value in industrial areas to
be complied with for
applications operated at supply
mains with nominal
currents≤100 A
A2.2
2.1
2.2
Category C2
1
st
environment
Class A;
group 1
Limit value in residential area or
at facilities at low-voltage mains
supplying buildings in residential
areas to be complied with
A1
3.1
3.2
Category C1
1
st
environment
Class B;
group 1
Limit value in residential areas
to be complied with
B1
4.1
4.2
Fig.11-4: Limit values for line-based disturbances