IEC / EN
61800-3
CISPR 11 Explanation
In this
document
Curves of
limit value
characteristic
Category C4
2
nd
environment
None
One of the following 3
requirements must have been
fulfilled:
Mains connection
current>400 A, IT mains or
required dynamic drive
behavior not reached by
means of EMC filter.
Adjust limit values to use and
operation on site.
User has to carry out and
provide evidence of EMC
planning.
None
Category C3
2
nd
environment
Class A;
group 2,
I>100 A
Limit value in industrial areas to
be complied with for
applications operated at supply
mains with nominal
currents>100 A
A2.1
1.1
1.2
Category C3
2
nd
environment
Class A;
group 2,
I≤100 A
Limit value in industrial areas to
be complied with for
applications operated at supply
mains with nominal
currents≤100 A
A2.2
2.1
2.2
Category C2
1
st
environment
Class A;
group 1
Limit value in residential area or
at facilities at low-voltage mains
supplying buildings in residential
areas to be complied with
A1
3.1
3.2
Category C1
1
st
environment
Class B;
group 1
Limit value in residential areas
to be complied with
B1
4.1
4.2
Fig.11-4: Limit values for line-based disturbances