17.2.3 Group b1: Basic Parameters
Basic running control
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
b1.00
First
frequency
setting
source
0: Given by panel potentiom‐
eter
1: Given by panel digital set‐
ting
2: Given by external analog
AIV
3: Given by external analog
AIC
4: Set by external UP/DOWN
terminals
5: Given via communication
6: Given by multi-speed
1 0 STOP
b1.01
Digital set
frequency
saving
0: Not saved when powered
off and stopped
1: Not saved when powered
off; saved when stopped
2: Saved when powered off;
not saved when stopped
3: Saved when powered off
and stopped
1 0 STOP
b1.02
First RUN
command
source
0: Inputting commands with
panel
1: Inputting commands via
external terminals
2: Inputting commands via
communication
1 0 STOP
b1.03 Reserved
b1.04
Digital set
frequency
[b1.07] ~ [b1.06] 0.01 Hz 50.00 Hz
RUN/
STOP
b1.05 Max. frequency 50.00 ~ 400.00 Hz 0.01 Hz 50.00 Hz STOP
b1.06
Upper
frequency
[b1.07] ~ [b1.05] 0.01 Hz 50.00 Hz
RUN/
STOP
DOK-RCON03-EFC-3600***-IT01-EN-P