● 1: Standard parameters. In this mode, parameters in group b and S (S0, S2 and S3)
are visible.
● 2: Extended parameters. In this mode, parameters in group b, S and E (E0, E1, E2,
E3 and E4) are visible.
● 3: Advanced parameters. In this mode, parameters in group b, S, E and H (H0) are
visible.
● 4: Start-up mode. The parameters in this mode are not additional parameters, but
only quick links to the respective parameters. See the table below for details:
Function code Name
[b0.21] Carrier frequency
[b1.00] First frequency setting source
[b1.02] First RUN command source
[b1.04] Digital set frequency
[b1.05] Max. frequency
[b1.06] Upper frequency
[b1.07] Lowest frequency
[b1.10] Direction control
[b1.20] Acceleration time 1
[b1.21] Deceleration time 1
[b1.22] Acceleration / deceleration curve mode
[b1.30] Starting mode
[b1.40] Stopping mode
[S0.00] V/F curve mode
[S2.00] Rated motor frequency
[S2.01] Rated motor rotation speed
[S2.02] Rated motor power
[S2.03] Rated motor voltage
[S2.04] Rated motor current
Fig.8-1: Parameters in start-up mode
● Monitoring parameter group is always visible.
● User password protection will not affect the modification of [b0.02].
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
54/235