b1.11 Operating panel controls direction
Setting range 0 ~ 1
Minimum unit 1
Factory default 0
This parameter is only applicable for operations via the operating panel.
0: Forward rotation
1: Reverse rotation
The relationship between [b1.10] and [b1.11] is:
Fig.8-3: Relationship between [b1.10] and [b1.11]
Direction control [b1.10] Default direction [b1.11] Final direction
0 Both directions
Forward Forward
Reverse Reverse
1 Forward only
Forward Forward
Reverse STOP with error
2 Reverse only
Forward STOP with error
Reverse Reverse
3 Inverse default direction
Forward Reverse
Reverse Forward
For "STOP with error", please see chapter 9.5 "Diagnosis on Errors" on
page 128.
Normally, each RUN / STOP command source has its own direction command source.
The generated direction is further controlled by internal direction control ([b1.10]).
Frequency source
RUN / STOP command
source
Direction command source
Multi-speed
Operating panel
Defined by multi-speed / PLC
configuration
2-wire / 3-wire running control
[E0.00]
2-wire / 3-wire running control
[E0.00]
Communication Communication
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings
63/235