S0.30 Current limitation control
Setting range
0: OFF
1: OFF at constant speed
3: ON at constant speed
Minimum unit 1
Factory default 0
S0.31 Automatic current limitation level
Setting range 20 % ~ 250 % (Rated frequency converter current)
Minimum unit 1 %
Factory default 200 %
S0.32 Current regulator proportion factor
Setting range 0.000 ~ 1.000
Minimum unit 0.001
Factory default 0.060
S0.33 Current regulator integrating time constant
Setting range 0.001 ~ 10.000
Minimum unit 0.001
Factory default 0.200
[S0.30]: Used to limit current, so that the tripping of frequency converter is avoided. The
function is useful for loads with large inertia or sudden changes.
3 modes of current limitation control can be selected:
[S0.30]=0: OFF.
Current limitation control will not be disabled in any case.
[S0.30]=1: OFF at constant speed.
Current limitation control works during Acc. and Dec., but does not work at constant
speed.
[S0.30]=3: ON at constant speed.
Current limitation control works in all cases: Acc., Dec. and constant speed.
The current regulator is a PI regulator with configurable P factor and I factor.
The higher set value of proportion factor [S0.32], the faster the current change will
be.
The higher set value of I factor [S0.33], the less accuracy of current suppression.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings