Factory default Depends on model
S2.11 Rotator resistance
Setting range 0.00 ~ 50.00 Ω
Minimum unit 0.01 Ω
Factory default Depends on model
S2.12 Leakage inductance
Setting range 0.00 ~ 200.00 mH
Minimum unit 0.01 mH
Factory default Depends on model
S2.13 Mutual inductance
Setting range 0.0 ~ 3000.0 mH
Minimum unit 0.1 mH
Factory default Depends on model
S2.14 No-load current
Setting range 0.00 ~ [S2.04]
Minimum unit 0.01 A
Factory default Depends on model
S2.15 Physical data calculation
Setting range 0 ~ 3
Minimum unit 1
Factory default 0
The motor parameters ([S2.00] ~ [S2.05]) must be set before using "Physical data cal‐
culation" [S2.15]. The necessary information can be found on the nameplate of motor.
[S2.15]=0: No action.
[S2.15]=1: Calculation. After the calculation is finished, parameters [S2.10] ~ [S2.14]
will be updated.
[S2.15]=2: Automatic adjustment while the motor is in static mode.
[S2.15]=3: Automatic adjustment while the motor is rotating.
S2.20
Sensor type
Setting range 0: PTC; 1: NTC
Minimum unit 1
Factory default 0
S2.21 Input channel of motor temperature
Setting range 0: Invalid; 1: Analog input voltage
Minimum unit 1