Fig.8-23: Jogging Acc. / Dec. time
Jogging command only comes from external terminals or communication.
When jogging command is activated, the motor runs with predefined frequency;
when the jogging command is inactive, the motor resumes the previous status.
If jogging forward and jogging reverse are active at the same time, the frequency
converter will STOP; if the jogging forward / reverse command is activated during
jogging reverse / forward, the frequency converter will STOP according to [b1.40]
“Stopping mode”.
S3.05 Skip frequency 1
Setting range 0.00 Hz ~ [b1.06]
Minimum unit 0.01 Hz
Factory default 0.00 Hz
S3.06 Skip frequency 2
Setting range 0.00 Hz ~ [b1.06]
Minimum unit 0.01 Hz
Factory default 0.00 Hz
S3.07 Skip frequency 3
Setting range 0.00 Hz ~ [b1.06]
Minimum unit 0.01 Hz
Factory default 0.00 Hz
S3.08 Skip frequency range
Setting range 0.00 ~ 30.00 Hz
Minimum unit 0.01 Hz
Factory default 0.00 Hz
To avoid the mechanical resonance, this function is implemented to define 3 skip fre‐
quencies. 3 skip frequencies are supported as shown in the figure below:
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
86/235