Setting range 1 % ~ 100 %
Minimum unit 1 %
Factory default 100 %
S3.30 Forward and reverse rotation dead zone time
Setting range 0.0 ~ 60.0s
Minimum unit 0.1s
Factory default 4.0s
[S3.30] represents the waiting time when the frequency converter switches from for‐
ward / reverse rotation to reverse / forward rotation. See the figure below for more infor‐
mation:
Fig.8-25: Forward and reverse rotation dead zone time
S3.32 UP / DOWN set velocity
Setting range 0.10 ~ 100.0 Hz/s
Minimum unit 0.01 Hz/s
Factory default 1.00 Hz/s
S3.33 UP / DOWN terminals initial frequency
Setting range 0 ~ [b1.06]
Minimum unit 0.01 Hz
Factory default 0.00 Hz
Used to change the output frequency. When [b1.00] or [b1.16] is set to 4, the UP /
DOWN control is activated as the command value. In this mode, the output frequency
can be adjusted easily with UP, DOWN and zeroing terminals. Please follow the follow‐
ing steps to adjust the output frequency.
1. Set [b1.00] / [b1.16]=4.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings
89/235

Table of Contents