[E2.30] Xi=15 Simple PLC status
=0 OFF Inactive
=0 ON Inactive
16: Simple PLC paused
When the terminal is switched on, the PLC running is paused and the frequency
converter runs at zero speed; when the terminal is switched off, the frequency con‐
verter resumes the status before the PLC pause. This function is dependent on the
level of the input terminal signal.
Step
Status of
Xi=16
Status of Xa
(RUN com‐
mand)
Status of
frequency converter
Comment
1 Inactive Active Run
2 Active Active
Decelerate to 0 Hz
(no stop DC braking)
Dec. time is based on
the current stage x con‐
figuration
3 Inactive Active
Accelerate to last
target stage
Acc. time is based on
last target stage x config‐
uration
4 Inactive Inactive Stop Stop according to [b1.40]
5 Inactive Active Run Restart from beginning
17: Reserved
18: The second frequency command source enabled
This function is used to switch frequency command source between the first channel
([b1.00]) and the second channel ([b1.16]), which is level-sensitive. When this func‐
tion is inactive, the first channel ([b1.00]) is active; when this function is active, the
second channel ([b1.16]) is active.
If status of external terminals for frequency source switching is changed during run‐
ning, the new frequency command is accepted and the frequency converter acceler‐
ates / decelerates to the new frequency command.
19: External fault N.O. contact input
20: External fault N.C. contact input
An external fault signal is connected to these terminals and if the signal is active, the
frequency converter indicates an “E-St” error and stops.
The reaction of the functions “External fault N.O. contact input” and “External fault
N.C. contact input” is defined as below:
N.C.:
If terminal is active (closed), there is no error.
If terminal is inactive (open), there is an error.
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
96/235