Code Name Setting range
FcP
default
myCro
default
F4.74
Pressure too low warning
level
0.0...300.0 bar 100.0 100.0
F4.75
Pressure too low warning
delay
0.0...100.0 s 60.0 60.0
d0.88 Warning type
0...10: See tab. 8-6 "Monitoring pa-
rameter" on page 75
11: Oxygen too high
12: System pressure too low
- -
E0.01 First run command source
0: Panel
1: Multi-function digital input
2: Communication
1 0
E0.45 Power loss restart mode
0: Inactive
1: Active for panel control
2: Active only for 2-wire control
0 1
E2.01 DO1 output setting 0...99
1: Convert-
er running
0: Convert-
er ready
E2.15 Relay1 output selection 0...99
14: Con-
verter error
15: Con-
verter OK
H8.05 EAI input mode
0: 0...20 mA
1: 4...20 mA
2: 0…10 V
3: 0…5 V
4: 2...10 V
5: -10...10 V
0 1
H8.20 EDO output setting
0...25
1: Convert-
er running
0: Convert-
er ready
H8.21
Extended relay output se-
lection
1: Convert-
er running
14: Con-
verter error
U1.00 Run monitoring display 0...99
0: Output
frequency
33: I/O card
EAI input
U1.10 Stop monitoring display 0...99
2: Setting
frequency
33: I/O card
EAI input
Tab. 7-28: Different parameter list between myCro and FcP default setting
Bosch Rexroth AG
Block Diagram of Main Functions
FcP 5020
60/83
DOK-RCON03-FCP5020****-QU04-EN-P