Code Name Setting range
FcP
default
myCro
default
F2.36 DO1 output 0: No function assigned from ASF
1: Converter warning
2: Green CytroPac flashing LED
3: Red CytroPac flashing LED
4: Oxygen too high (for myCro)
5: Pressure too low (for myCro)
1 4
F2.37 EDO output 0 5
F2.38 EDO2 output
0: No function assigned from ASF
1: Converter warning
2: Green CytroPac flashing LED
3: Red CytroPac flashing LED
4: Oxygen too high (for myCro)
5: Pressure too low (for myCro)
6: Degas/gas valve control (for my-
Cro)
0 0
F3.12 Proportional gain [0] 0.00...500.00 rpm/bar 8.00 2.00
F3.13 Integral time 1 [0] 0...999 ms 80 200
F3.16 Differential gain [0] 0.000...10.000 (rpm/bar)*s 0.000 0.000
F3.19 System minimum speed [0] -5,000...5,000 rpm 0 500
F3.32 Proportional gain [1] 0.00...500.00 rpm/bar 8.00 2.00
F3.33 Integral time 1 [1] 0...999 ms 80 200
F3.36 Differential gain [1] 0.000...10.000 (rpm/bar)*s 0.000 0.000
F3.39 System minimum speed [1] -5,000...5,000 rpm 0 500
F3.40
Pressure command arrived
threshold
0.1...1000.0 bar 5.0 5.0
F4.17
Maximum system pressure
warning time delay
0.0...6000.0 s 0.0 60.0
F4.18
Maximum pump pressure
error time delay
0.0...6000.0 s 0.0 60.0
F4.70
Drive start level via AI (for
myCro)
0.0...20.0 V, mA 14.2 14.2
F4.71
Drive stop level via AI (for
myCro)
0.0...20.0 V, mA 10.4 10.4
F4.72
Oxygen too high warning
level
0.0...20.0 V, mA 15.5 15.5
F4.73
Oxygen too high warning
delay
0.0...100.0 hours 4.0 4.0
FcP 5020 Bosch Rexroth AG
Block Diagram of Main Functions
DOK-RCON03-FCP5020****-QU04-EN-P
59/83