Specifications and Site Preparation Polycold Cryochiller
Electrical Installation and Operation Manual
Brooks Automation
3-4
214072 Revision B
Electrical
Electrical Characteristics - MaxCool 4000H and MaxCool 2500L
Table 3-2: Nominal and Maximum Power
Parameter MaxCool 4000H MaxCool 2500L
Power Input at Max Rated Load
19.2 kW
@ 4000 watts
19.2 kW
@ 2500 watts
Power Input with Cool and Low Load
12.4 kW
@ 0 to 300 watts
13.9 kW
@ 0 to 300 watts
Standby Power 12 kW 11.4 kW
Table 3-3: For units with Power Management Option Enabled
Parameter MaxCool 4000H MaxCool 2500L
Power Management Cool at 2/3 Max Rated Load 14 kW 14.9 kW
Power Management Cool with No Load 9.2 kW 12.4 kW
Power Management in Standby 10.1 kW 9.9 kW
Table 3-4: MaxCool 4000H and 2500L Cryochiller Electrical Characteristics
Compressor
Voltage
Range
Transformer
Tap Setting
Common Nominal
Voltages Worldwide
(Voltage-Phase-Frequency)
Voltage Range
200-230 VAC
200-3-50/60
200-3-50
202-3-60
208-3-60
180-222 @ 50 Hz
182-229 @ 60 Hz
230-3-60 230-3-60
207-230 @ 50 Hz
207-253 @ 60 Hz
380-480 VAC
380-3-50 380-3-50 342-418 @ 50 Hz
400-3-50
400-3-50
415-3-50
360-440 @ 50 Hz
460-3-60
440-3-60
460-3-60
414-506 @ 60 Hz
480-3-60 480-3-60 432-528 @ 60 Hz
575 VAC 575-3-60 575-3-60 518-632 @ 60 Hz