Operating Instructions
160
AUT
180
140
120
AUTOMATIC
11.15am
71
Boiler Controls
Logamatic 2107
6 720 618 081 - 08/2008 US/CA
For the user
Please read carefully before
use.

Other manuals for Buderus Logamatic 2107

Questions and Answers

  • N
    Nancy CooperSep 16, 2025
    Why is my Buderus Network Router showing a supply temperature sensor 2 error MIX SENSOR ERROR?
    • U
      uperkinsSep 16, 2025
      A supply temperature sensor 2 error could indicate a defective sensor or an interrupted connecting cable. Examine the sensor connection and replace the sensor if necessary.
  • R
    Roberta JordanSep 16, 2025
    What does collector sensor error SL SENSOR ERROR mean on my Buderus Network Router?
    • C
      Connie BarrySep 17, 2025
      A collector sensor error may be caused by a defective sensor, a defective Solar module (FM 244), or an interrupted connecting cable. Check the sensor connection, replace the sensor and replace the module.
  • C
    Charles ParkerSep 18, 2025
    What should I do if I see a solar hot water sensor error DHW-SL ERROR on my Buderus Network Router?
    • J
      Joshua MejiaSep 18, 2025
      A solar hot water sensor error may be due to a defective sensor, a defective Solar module (FM 244), or an interrupted connecting cable. Check the sensor connection, replace the sensor and replace the module.
  • S
    Sean JamesSep 18, 2025
    What does FM 244 error (solar card) FM 244 ERROR mean on a Buderus Network Router?
    • M
      Michelle MartinSep 19, 2025
      The FM 244 error indicates that the module is no longer present or is defective. Log the module off, plug the module in again, or replace the module.
  • L
    Lindsay RobertsonSep 23, 2025
    What causes FM 241 error (mixing card) FM 241 ERROR on a Buderus Network Router?
    • A
      ashleyrhodesSep 23, 2025
      The FM 241 error suggests the module is either no longer present or is defective. Log the module off, plug the module in again, or replace the module.
  • F
    fmooreSep 23, 2025
    How to troubleshoot FM 242 error (burner card) FM 242 ERROR on Buderus Network Router?
    • R
      rebecca33Sep 23, 2025
      The FM 242 error indicates that the module is no longer present or is defective. Log the module off, plug the module in again, or replace the module.
  • A
    Alexander SmithSep 23, 2025
    How to troubleshoot Domestic Hot Water - DHW PROD ERR on Buderus Network Router?
    • M
      mitchelltammySep 23, 2025
      Turn the power off to the R2107 to reset. Check terminals 24 & 25 for 120V. If power is present and boiler fires the R2107 is o.k. Check the following: 1 - bad circulator 2 - stuck flow check 3 - piping is air bound 4 - closed valve
  • T
    Tracy MathewsAug 23, 2025
    How to fix 'BURNER ERR' on Buderus Logamatic 2107?
    • J
      Jennifer RobertsAug 23, 2025
      To address the 'BURNER ERR' message on your Buderus Control Systems, reset the burner as described in the boiler or burner documentation.
  • A
    Adam BuckleySep 6, 2025
    What to do if my Buderus Control Systems display shows 'DHW PROD ERR'?
    • E
      Edwin AndersonSep 6, 2025
      If the Buderus Control Systems displays 'DHW PROD ERR', switch the emergency mode switch to "Manual". In emergency mode, the heating system will operate without the electronic program, and the DHW temperature will be determined by the boiler water temperature. The DHW priority circuit will be disabled. Turn the boiler water thermostat to 140°F (60°C), and afterwards consult your local heating contractor.
  • D
    Daniel ArmstrongSep 5, 2025
    What to do if my Buderus Logamatic 2107 display shows 'HEATING ERR'?
    • S
      scott88Sep 5, 2025
      If your Buderus Control Systems display shows 'HEATING ERR', it could be due to a faulty electronic circuit, the boiler water thermostat being set too low, or the high limit safety cut-out having responded. In any of these cases, you should consult your local heating contractor.

Summary

Using the Controls Safely

Correct Use of Logamatic Controls

Ensures the Logamatic 2107 controls is operated as intended and in perfect working order.

Safety Precautions for Heating System

Highlights risks of scalding, system damage from frost, and life risks from electrical hazards.

Navigating Your Controls

Basic Heating Functions

Switching the Controls ON

Procedure to start up the Logamatic 2107 controls by setting switches and pressing the 'AUT' key.

Changing the Operating Mode

Explains automatic and manual modes for heating and DHW operation.

Setting the Room Temperature

Guides on setting room temperature for normal and setback modes, with or without remote controls.

Setting the DHW Temperature

Instructions on how to set the domestic hot water (DHW) temperature.

Extended Functions for Heating Control

Entering a Vacation Program

How to set a temporary heating program for periods of absence to save energy.

BFU Remote Control Operation

Advanced Programming Options

Modifying Standard Heating Programs

Customizing existing heating programs or creating new ones to meet specific needs.

Creating a New Heating Program

Step-by-step guide to setting up entirely new, personalized heating schedules.

Troubleshooting Heating System Faults

Heating System Fault Table

Lists common fault messages, their effects, and remedies, including contractor consultation.

Operation During a Fault

Flue Gas Test Procedure

Buderus Logamatic 2107 Specifications

General IconGeneral
CategoryControl Systems
TypeHeating Control Unit
Voltage230 V
Frequency50 Hz
Protection classIP20
Ambient temperature0°C
ApplicationHeating systems