7
English
Basicsafetyinformation
Thissafetyinformationdoesnottakeintoaccount:
anycontingenciesoroccurencesthatmayariseduringassembly,•
useandmaintenanceofthedevices.
thelocalsafetyregulationsthattheoperatormustensurethestaff•
inchargeofassemblyand/ormaintenanceobserve.
Whenthe1062isusedinanATEX21or22zone,makesure:
Thatthecoveroftheelectricalpositionfeedbackisalways•
screwedshutbeforeoperatingthevalve.
Thatyoucheckthatthedeviceisnotsubjecttoaflowofairand•
dustthatmayresultinanaccumulationofelectrostaticcharges.
Otherwise,intallthedeviceinaconductivecover.
"TheNAMURswitchesonthe1062mustbepoweredbya•
voltagesourceofatypecertifiedforuseinexplosiveatmos-
pheresingroupsIIB/IICandtheircombinationmustbecompa-
tiblefromtheinstrinsicsafetypointofview."
Shutdownthepneumaticpowersourceanddepressurisethe•
pipesbeforecarryingoutworkonthedevice.
Beforestartingwork,switchoffthepowersupplyandsecureit•
topreventrestarting.
Observeallapplicableaccidentprotectionandsafetyregula-•
tionsforelectricalequipment.
Toavoidinjurytakecareto:
preventanypowersupplyswitch-on.•
ensurethatinstallationandmaintenanceworkarecarriedoutby•
qualifiedandskilledstaffwiththeappropriatetools.
guaranteeasetandcontrolledrestartingoftheprocess,after•
anelectricaland/orpneumaticpowersupplyinterruption.
usethedeviceonlyifinperfectworkingorderandincom-•
pliancewiththeinstructionsprovidedintheusermanual.
observethegeneraltechnicalruleswhenlocatingandusingthe•
device.