14

English
Technicaldata
Versionwithdouble
inductiveswitch(4-wire)
statusesdetected•
valveopenorclosed•
indicationmode
colourofthelights•
dependingonthe
statusdetected
poweruplight•
valveopenandvalveclosed•
usinglightsandelectricalsignalvia•
terminalblock
anorangelightcomesonwhenthe•
valveopensandaredlightcomeson
whenthevalvecloses
green•
Versionwithdouble
inductive2-wireNAMUR
switch
statusesdetected•
valveopenorclosed•
indicationmode
colourofthelights•
dependingonthe
statusdetected
valveopenandvalveclosed•
usinglightsandelectricalsignalvia•
terminalblock
anorangelightgoesoffwhenthe•
valveopensandaredlightgoesoff
whenthevalvecloses


Pollutiondegree 2
Installationcategory I
Altitudemax. 2000m
Electricpower suppliedbyanSELV(SafetyExtraLow
Voltage)source

Connectioncable standard,diameterbetween5and
7mm,maxcross-sectionofthestrand
1mm
2
Mechanicalcontact
version(percontact)
Powersupplyof•
devicesapprovedby
CSAandCE
Powersupply•
ofdevicesonly
approvedbyCE
Powerconsumption•
Allowableload•
Typeofoutput•
12-30VACor•
12-48VDC
12-30VDCor•
12-48VDC/VACor
48/110VDC/VACor
110/250VDC/VAC
<35mA(48VDC)•
<8mA(220VAC)
dependingonthepowersupply•
voltageandthetypeofload,inductive
orresistive:seeTable 1:nextpage
contactnormallyopenornormally•
closed