10.1.5 SecsPerRecord
Reports the data output interval for a data table.
10.1.6 SkippedRecord
Reports how many times records have been skipped in a data table. Array elements are in the
order that data tables are declared in the CRBasic program. Enter 0 to reset.
10.1.7 TimeStamp
Scan time that a record was generated.
l NSEC data type
10.2 Status table system information
The Status table is an automatically created data table. View the Status table by connecting the
data logger to your computer (see Making the software connection (p. 43) for more information).
Most fields in the Status table are read only and of a numeric data type unless noted. Error
counters (for example, WatchdogErrors or SkippedScan) may be reset to 0 for troubleshooting
purposes.
Status table values may be accessed programatically using SetStatus() or
Tablename.Fieldname syntax. For example: Variable = Status.Fieldname. For
more information see:https://www.campbellsci.com/blog/programmatically-access-stored-data-
values.
10.2.1 Battery
Voltage (VDC) of the battery powering the system. Updates once per minute, when viewing the
Status table, or programatically.
10.2.2 BuffDepth
Shows the current pipeline mode processing buffer depth, which indicates how far the
processing task is currently behind the measurement task. Updated at the conclusion of scan
processing, prior to waiting for the next scan.
10.2.3 CalCurrent
Shows the offset calibration factor for the resistor used in 0-20 and 4-20 mA measurements on
RG terminals. Measured once during production calibration.
10. Information tables and settings (advanced) 165