10.2.13 CompileResults
Contains messages generated at compilation or during runtime. Updated after compile and for
runtime errors such as variable out of bounds.
l String data type
10.2.14 ErrorCalib
Number of erroneous calibration values measured. Erroneous values are discarded. Updated at
startup.
10.2.15 FullMemReset
Enter 98765 to start a full-memory reset, all data and programs will be erased.
10.2.16 IxResistor
Factory-calibrated correction factor (in units of ohms) applied to resistance measurements.
Normal value is near 1000 ohms. Updates at start up.
10.2.17 LastSystemScan
Reports the time of the of the last auto (background) calibration, which runs in a hidden slow-
sequence type scan. See MaxSystemProcTime, SkippedSystemScan, and SystemProcTime.
10.2.18 LithiumBattery
Voltage of the internal lithium battery. Updated at CR6 power up. For battery information, see
Internal battery (p. 116).
10.2.19 Low12VCount
Counts the number of times the primary CR6 supply voltage drops below ≈9.0 VDC. Updates
with each Status table update. Range = 0 to 99. Reset by entering 0. Incremented prior to scan
(slow or fast) with measurements if the internal hardware signal is asserted.
10.2.20 MaxBuffDepth
Maximum number of buffers the CR6 will use to process lagged measurements. Enter 0 to reset.
10. Information tables and settings (advanced) 167