EasyManuals Logo

Carel mastercella User Manual

Carel mastercella
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
57
ENGLISH
ir33 +030220441 - rel. 2.0 - 01.05.2006
A8 Digital input 3 confi guration -SYF ag C 0 1 0
A9 Light management mode with door switch - C 0 14 0
Ado High condenser temperature alarm MSYF ag C 0 1 0
Ac High condenser temperature alarm
differential
-SYF °C/°F C 0.0 200 70.0
AE High condenser temperature alarm delay -SYF °C/°F C 0.1 20 5.0
Acd High condenser temperature alarm delay -SYF min C 0 250 0
AF Light sensor OFF time -SYF sec C 0 250 0
ALF Antifreeze alarm threshold MSYF °C/°F C -50 200 -5.0
AdF Antifreeze alarm delay MSYF min C 0 15 1
Code Parameter MSYF ** UOM Type Min Max Def.
F0 Fan management ---F ag C 0 2 0
F1 Fan start temperature ---F °C/°F F -50 200 5.0
F2 Fan OFF with compressor OFF ---F ag C 0 1 1
F3 Fans in defrost ---F ag C 0 1 1
Fd Fan OFF after dripping ---F min F 0 15 1
F4 Condenser fan stop temperature MSYF °C/°F C -50 200 40
F5 Condenser fan start differential MSYF °C/°F C 0.1 20 5.0
Code Parameter MSYF ** UOM Type Min Max Def.
H0 Serial address MSYF - C 0 207 1
H1 Function of relay 4 MSYF ag C 0 13 1
H2 Disable keypad/IR MSYF ag C 1 6 1
H3 Remote control enabling code MSYF - C 0 255 0
H4 Disable buzzer MSYF ag C 0 1 0
H5 Function of relay 5 - C 0 10 3
H6 Lock keypad MSYF - C 0 255 0
H8 Select activation of output with time band MSYF ag C 0 1 0
H9 Enable set point variation with time band MSYF ag C 0 1 0
Hdh Anti-sweat heater offset MSYF °C/°F C -50 200 0.0
Code Parameter MSYF UOM Type Min Max Def.
HAn Number of HA events recorded MSYF - C 0 15 0
HA Date/time of last HA event MSYF - C - -
y__ Year **** Years * 0 99 0
M__ Month **** Months * 1 12 0
d__ Day **** Days * 1 7 0
h__ Hours **** Hours * 0 23 0
n__ Minutes **** Min. * 0 59 0
t__ Duration **** Hours * 0 99 0
HA1 Date/time of penultimate HA event MSYF - C - - -
HA2 Date/time of third from last HA event MSYF - C - - -
HFn Number of HF events recorded MSYF - C 0 15 0
HF Date/time of last HF event MSYF - C - - -
y__ Year **** Years * 0 99 0
M__ Month **** Months * 1 12 0
d__ Day **** Days * 1 7 0
h__ Hours **** Hours * 0 23 0
n__ Minutes **** Min. * 0 59 0
t__ Duration **** Hours * 0 99 0
HF1 Date/time of penultimate HF event MSYF - C - - -
HF2 Date/time of third-to-last HF event MSYF - C - - 0
Htd HACCP alarm delay MSYF min C 0 250 0
Code Parameter MSYF UOM Type Min Max Def.
td1 Defrost time band 1 -SYF - C - - -
d__ Day **** Days * 0 11 0
h__ Hours **** Hours * 0 23 0
n__ Minutes **** Min. * 0 59 0
td2 Defrost time band 2 -SYF - C - - -
td3 Defrost time band 3 -SYF - C - - -
td4 Defrost time band 4 -SYF - C - - -
td5 Defrost time band 5 -SYF - C - - -
td6 Defrost time band 6 -SYF - C - - -
td7 Defrost time band 7 -SYF - C - - -
td8 Defrost time band 8 -SYF - C - - -
ton Light/aux on time band -SYF - C - - -
d__ Day **** Days * 0 11 0
h__ Hours **** Hours * 0 23 0
n__ Minutes **** Min. * 0 59 0
toF Light/aux off time band -SYF - C - - -
d__ Day **** Days * 0 11 0
h__ Hours **** Hours * 0 23 0
n__ Minutes **** Min. * 0 59 0
tc RTC date/time setting MSYF - C - - -
y__ Year **** Years 0 0 99 00
M__ Month **** Months 1 1 12 1
d__ Day of the month **** Days 1 1 31 1
u__ Day of the week **** Days 6 1 7 6
h__ Hours **** Hours 0 0 23 0
n__ Minutes **** Min. 0 0 59 0
Note: the visibility of the parameters may vary according to the models:
- mastercella model A = same default confi guration as ir33, ir33power, ir33DIN, powercompact
and powercompact small model S;
- mastercella model D, and model C and M of the other instruments, same confi guration as model F.

Table of Contents

Other manuals for Carel mastercella

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel mastercella and is the answer not in the manual?

Carel mastercella Specifications

General IconGeneral
SeriesMastercella
Front ProtectionIP65
Protection RatingIP65 (front)
Control TypePID, ON/OFF
DisplayLCD
InputsNTC, PT1000
OutputsRelay, SSR
Storage Temperature-30°C to +70°C
Analogue Outputs4-20 mA, 0-10 V
Serial CommunicationRS485, Modbus RTU
Relative Humidity<90% RH non-condensing

Related product manuals