116  Installation and Programming Guide 
 
2.  Enter an Account Number up to 8 digits, hex values are accepted. 
3.  Select the Format of the communication channel, this will automatically use the settings 
programmed for that Format in the Communicator menu.  
If reporting to a control room via UltraSync, this must be set to “UltraSync”. 
4.  Select the reporting device, by default Device 1 is the Aritech Reliance XR panel. 
5.  Enter the destination email address or IP address depending on which Format you 
selected. 
If reporting to a control room via UltraSync, this can be left blank for SIA or CID event 
messages. 
6.  Select what events you want to be sent via this Channel by selecting the appropriate 
Event List. Events that arrive at this channel will be checked that they on this Event List, 
if they are, then will be routed through this Channel. Events that arrive at this Channel 
which are not on this list will be blocked. 
If the currently selected Channel is used for push notifications to UltraSync+ app, the 
Event List number must be the same as the Channel number. 
7.  Enter the number of Attempts that you want Aritech Reliance XR to try sending the 
event message on this Channel before switching to the Next Channel. 
8.  Select the Next Channel Number to use if the event message fails to be sent on this 
Channel.  
Each Channel can have one Next Channel as a backup. This allows you to chain up to 15 
backup paths should the primary one fail. Enter Next Channel as 0 to end the chain of 
channels.  
9.  You have now finished programming one channel. If you entered a Next Channel, then 
go to that Channel number and program that now.