Installation and Programming Guide  31 
Alternatively, from the web server: 
1.  Log in to the web server as installer. 
2.  Click Advanced. 
3.  Click Shortcut. 
4.  Enter 910.910 
5.  Press OK. 
6.  Log out of panel 
DLX900 can load default configuration if it can connect to the panel (requires valid 
download access code). 
1.  Open DLX900. 
2.  Connect to the desired panel. 
3.  Click Control Panel – Default control data from – Factory defaults. 
4.  Click Yes – all exiting programming for currently selected customer will be replaced with 
factory settings. 
5.  Click Send All Data. 
6.  Before disconnecting ensure Download Access Code, Web Access Code, and Installer 
PIN are set. Otherwise, you may not be able to reconnect. 
Defaulting Installer Account 
The installer PIN can be reset to factory default if physical access is available: 
1.  Disconnect power. 
2.  Hold down the LEARN button on the panel. 
3.  Connect power. 
4.  Continue holding the LEARN button for 10 seconds. 
5.  Release LEARN button. 
6.  Installer PIN will be reset to factory default.