Address Description Unit Type
2104 Phase 2 voltage V/10 S32/float
2106 Phase 2 current A/10 S32/float
2108 Phase 2 frequency Hz/100 S32/float
2110 Reserved
2112 Phase 2 worse power factor % S32/float
2114 Phase 2 worse temperature °C/10 S32/float
2116 Phase 2 load ratio (W) % S32/float
2118 Phase 2 load ratio (VA) % S32/float
2120 Phase 2 available true power W S32/float
2122 Phase 2 available apparent power VA S32/float
Output phase 3
2150 Phase 3 true power W S32/float
2152 Phase 3 apparent power VA S32/float
2154 Phase 3 voltage V/10 S32/float
2156 Phase 3 current A/10 S32/float
2158 Phase 3 frequency Hz/100 S32/float
2160 Reserved
2162 Phase 3 worse power factor % S32/float
2164 Phase 3 worse temperature °C/10 S32/float
2166 Phase 3 load ratio (W) % S32/float
2168 Phase 3 load ratio (VA) % S32/float
2170 Phase 3 available true power W S32/float
2172 Phase 3 available apparent power VA S32/float
Input Group 1 Phase 1
Reserved Phase true power W S32
Reserved Phase apparent power VA S32
Reserved Phase voltage V/10 S32
Reserved Phase current A/10 S32
Reserved Phase frequency Hz/100 S32
Input Group 1 Phase 2
Reserved Phase true power W S32
Reserved Phase apparent power VA S32
Reserved Phase voltage V/10 S32
Reserved Phase current A/10 S32
Reserved Phase frequency Hz/100 S32
Input Group 1 Phase 3
Reserved Phase true power
W S32
Reserved Phase apparent power VA S32