INST.No.INE-868G [DB600] General Instruction Manual
- 112 -
5-13 MODEd [External input parameter]
5-13-1
Setting overview
MODEd provides the settings related to the external signal input. The display is available only for the
specification with external signal input.
External input is enabled by setting a function available for assignment to the external no voltage contact
input number.
See the section 6-11 for details.
5-13-2
Setting item screen and function
Setting item Function
□□□
▲
SEL
↑ ↓
▼
SEL
Initial screen
MODEd initial screen
(External input
parameter)
MODEd (external input parameter) initial screen
Pressing the [
∨
] key makes a switch to the MODEc, MODEb, MODE7 or MODE6
screen.
Pressing the [
∧
] key makes a switch to the MODEt screen.
No parameter is set by the [ENT] key.
[Switch to operation initial screen]
Press and hold the [MODE] key to display the screen set on the MODEt operation
initial screen.
□□
□□
▲
SEL
↑ ↓
▼
SEL
External input
External input 1 Sets the external input 1.
"
□□
"
Function OFF. No external signal input assigned.
"
"
[Constant value operation] RUN/READY switch
"
"
AUTO/MANUAL output switch
"
"
Preset manual
"
"
Timer 1
"
"
Timer 2
"
"
Alarm event reset
"
□
"
Execution No. selection 1 for constant value operation (Bit0)
"
□
"
Execution No. selection 2 for constant value operation (Bit1)
"
□
"
Execution No. selection 4 for constant value operation (Bit2)
"
□
"
Execution No. selection 8 for constant value operation (Bit3)
Program operation specifications
"
"
Program/constant value operation switch
"
□
"
Program operation RUN/STOP
"
□
"
Program operation ADVANCE
"
"
Program operation RESET
"
"
Program pattern 1 (Bit0)
"
"
Program pattern 2 (Bit1)
"
"
Program pattern 4 (Bit2)
*If program/ constant value operation switch is following setting, external input
functions below do not work.
•
In the case of "OFF" (constant value operation)
Program operation RUN/STOP, Program operation ADVANCE, Program
operation RESET, Program pattern 1/2/4
•
In the case of "ON" ( program operation)
RUN/READY switch, Execution No. selection for constant value operation 1/2/4/8
Use the [
∨
], [
∧
] and [ENT] keys to set the external input 1.
□□
□□
▲
SEL
↑ ↓
▼
SEL
External input 2 Sets the external input 2.
Use the [
∨
], [
∧
] and [ENT] keys to set the external input 2.