INST.No.INE-868G [DB600] General Instruction Manual
- 156 -
9 Appendix
9-1 Specifications
Input specifications
Input signal:
Thermocouple B, R, S, N, K, E, J, T, U, L,
C(WRe5-WRe26), W-WRe26, Platinel II,
PtRh40-PtRh20, Au-Pt
DC voltage ±20mV, ±100mV, ±5V, ±10V
Resistance
thermometer
Pt100, JPt100, Pt50
Measuring range Thermocouple 16 types, DC voltage 4
types, resistance thermometer 5 types
Temperature unit °C
Accuracy rating ±0.1% of FS ±1digit of measuring range
See " Input type, measuring range and
accuracy rating" for details.
Reference junction
compensation
accuracy
±1.0°C (ambient temperature 23°C ±10°C)
±2.0°C (temperatures other than above)
Sampling rate Approx. 0.1 seconds
Burnout Higher limit burnout is provided for
thermocouple, resistance thermometer and
DC voltage (20mV) only as standard.
Output 1 produces PV abnormal output and
output 2 is fixed to 0% when burnout
occurs. Higher limit alarm event is output.
Input resistance Thermocouple 1MOhm or more
DC voltage Approx. 1MOhm
Allowable signal
source resistance
Thermocouple 100Ohm or less
DC voltage (mV) 100Ohm or less
DC voltage (V) 300Ohm or less
Allowable wire
resistance
Resistance thermometer 10Ohm/1 wire or
less (resistance of 3 wires should be equal
to one another)
Resistance
thermometer
measurement current
Approx. 1mA
Allowable input voltage Thermocouple ±10V DC
DC voltage (mV) ±10V DC
DC voltage (V) ±20V DC
Resistance thermometer ±5V DC
Transient overvoltage 1500V
* This is a reference safety standard value
for UL/CSA61010-1, UL61010-2-030.
This value is not necessarily a guarantee
of instrument performance.
Maximum common
mode voltage
30V AC
Common mode
rejection ratio
130dB or more (50/60Hz)
Series mode rejection
ratio
50dB or more (50/60Hz)
Display specifications
Display Segment type LCD
(LED backlight)
Control specifications
Control interval Approx. 0.1 seconds
Output type ON-OFF pulse output, ON-OFF servo
output (DB650 and DB670 only), current
output, SSR drive pulse output, voltage
output
ON-OFF pulse output type:
Contact type 1a contact
Pulse cycle Approx. 1 to 180 seconds
Contact capacity Resistive load 240V AC 3A
30V DC 3A
Inductive load 240V AC 1.5A
30V DC 1.5A
Minimum load 5V DC 10mA
ON-OFF servo output type:
Contact type 1a contact
Feedback resistance 100Ohm to 2kOhm
Contact capacity Resistive load 240V AC 3A
30V DC 3A
Inductive load 240V AC 1.5A
30V DC 1.5A
Minimum load 5V DC 10mA
Current output type:
Output specification 4 to 20mA DC
Load resistance 600Ohm or less
SSR drive pulse output type:
Pulse cycle Approx. 1 to 180 seconds
Output specification ON 12V DC ±20%
(load current 21mA or less)
OFF 0.8V DC or less
Voltage output type:
Output specification 0 to 10V DC
Output resistance Approx. 10Ohm
Load resistance 50kOhm or more
Specification with 2 outputs:
Output type Any combination between ON-OFF pulse,
output, current output and voltage output is
possible.
Insulation Non-isolated between 2 outputs (ON-OFF
pulse output type excluded)
Control system PID, split
Event function
Alarm event
(EV1 to 4)
Absolute value alarm, deviation alarm,
absolute value deviation alarm, set point
alarm, output value alarm, heater
disconnection alarm (only for the case
adjustment output 1 uses ON-OFF pulse
output or SSR drive pulse output), timer 1,
timer 2, FAIL
Status event
(EV1 to 9)
Constant value operation RUN, preset
manual, remote input, SV rise, SV fall
Program function:
Step switching, step 1 to 12, RUN, STOP,
ADVANCE, RESET, END, SV keep