INST.No.INE-868G [DB600] General Instruction Manual
- 120 -
6-3 Alarm event type
The alarm event comes in a variety of types as shown below.
PV: Measured value SV: Setting value
AL: Event value db: Event deadband
Event output range with "Event standby" set
Normal event output range
Event activation range
Absolute value higher limit alarm
Higher limit alarm against a measured value (PV).
Activation condition
AL < PV
Keep condition
AL - db < PV ≤ AL
Reset condition
PV ≤ AL - db
Absolute value lower limit alarm
Lower limit alarm against a measured value (PV).
Activation condition
AL > PV
Keep condition
AL ≤ PV < AL + db
Reset condition
PV ≥ AL + db
Deviation higher limit alarm
Higher limit alarm against the difference between a setting value (SV) and measured value (PV).
Activation condition
PV > SV + AL
Keep condition
SV + AL - db < PV ≤ SV + AL
Reset condition
PV ≤ SV + AL - db
Deviation lower limit alarm
Lower limit alarm against the difference between a setting value (SV) and measured value (PV).
Activation condition
PV < SV + AL
Keep condition
SV + AL ≤ PV < SV + AL + db
Reset condition
PV > SV + AL + db
Event deadband (db)
Event deadband (db)
Powe
-ON
Powe
-ON
Powe
-ON
Power-ON
Event deadband (db)
Event value (AL)
Event deadband (db)
Event value (AL)