8 Maintenance and inspection
8-1 Error display
When an error occurs in the system, the error No. shown below will be displayed for approx. two seconds.
Check the error contents and contact the dealer or your nearest CHINO office.
Error No. Error contents

A/D conversion error of PV/RJ

A/D conversion error of feedback/remote signal input

Calibration data error
While the error is displayed, each function performs the following operations.
Item


(Feedback error)

(Remote error)

Measured value (PV) Stop updating values Stop updating values Stop updating values Normal operation
Feedback measured
value
Normal operation Stop updating values Normal operation Normal operation
Remote SV input Normal operation Normal operation Stop updating values Normal operation
Control output Normal operation Normal operation Normal operation Normal operation
Event output Normal operation Normal operation Normal operation Normal operation
Transmission output Normal operation Normal operation Normal operation Normal operation
Communication Normal operation Normal operation Normal operation Normal operation
External signal input Normal operation Normal operation Normal operation Normal operation
8-2 Warning display
When an inappropriate setting or operation is performed, the warning No. shown below will be displayed
for approx. three seconds. Check the warning contents and try appropriate setting or operation.
Warning No. Warning contents

Program operation cannot be executed.
Check that the program pattern is set correctly.

Feedback tuning fails or the zero adjustment value of servo exceeds the span
adjustment value.
Check the feedback input line if the connection is done properly for the OPEN
and CLOSE sides.

Key lock is active. Set "Key lock (MODEt)" to "Function OFF".
When a parameter is changed during a writing process via communication, the
key lock becomes active temporarily to restrict the key operation. To change a
parameter by keys, stop the writing process via communication, and change the
screen once using the [SEL] or [SEL] key.
Caution
- [LOCK] display while in communication -
While writing (WRITE) parameter using communication, operation,
setting, or changing setting by key operation are restricted by
displaying [LOCK]. To set or change setting from the instrument,
[ENT] key becomes available after stop issuing WRITE command then
change the screen using the [
SEL] or [
SEL] key.